Technical Specifications | |
---|---|
Capacity 1ø | SP15KVA – 30KVA |
System | Single-phase - Air Cooled |
Output Voltage | 230 VAC ±1% |
Input voltage variation | ±20%VAC Of O/p Voltage (180 VAC to 280 VAC) |
Input voltage range | 170VAC - 270VAC |
Max input current | 96Amp - 143Amp |
Rated output current | 87Amp - 130Amp |
Efficiency | >98.5% |
Voltage Correction | 5000V/Sec |
Dimensions LxWxH | 395x570x435mm |
Weight | 40 Kg |
Standard Features | |
---|---|
Voltage | IGBT controlled / Pulse Width Modulation (PWM)/ Digital Signal Processing (DSP) |
Selectable output voltage | 210VAC-220VAC-230VAC-240VAC (L-N) |
Frequency | 50Hz ±5% or 60Hz ±5% |
Output voltage accuracy | ±0.5% to ±2% |
Cooling | Forced ventilation |
Operating temperature range | -20/+50°C |
Storage temperature | -20/+60°C |
Admitted overload | 150% For 2sec |
Color | RAL 7035 (Light Grey) |
Protection degree | IP20 |
Instrumentation | Output digital relay |
Installation | Indoor |
Overvoltage protection | Class II output surge arrestors |
Protections | EMI/RFI filters and Input circuit breakers |
Application Areas | 1) Industrial Automation 2) Medical Equipment 3) IT &Telecommunication 4) Commercial Buildings 5) Residential 6) Agriculture |